Configuring a Modbus Plus Network in Concept with Peer Cop
326
870USE10110 July 2004
3 Type the value 1 in the Length column, indicating that the device at address 3 will
supply one word of data. In this case, we will leave the default BIN setting.
4 Repeat steps 2 and 3 for the device at address 5, using the settings in the figure
below. Then click <OK>.
Step Action
Specific Onput
OK
Cancel
Help
Range: 400001-401872 1-32
Dest. Node Source Ref. Length Bin/BCD
1
2
3 400016 1 BIN
4
5
6
7
8
9
10
11
12
Specific Onput
OK
Cancel
Help
Range:
Dest. Node Source Ref. Length Bin/BCD
1
2
3 400016 1 BIN
4
5 400017 2 BIN
6
7
8
9
10
11
12
Vedere la pagina 325