Using Peer Cop with Modsoft
222
870 USE 101 00 V.2.2
Specifying References for Input and Output Data,
Continued
Defining the
Specific Output,
Continued
Continued on next page
Step Action
3 In the LEN column of the SPECIFIC OUTPUT field, type the value
8
, indicating that
the the M1 CPU at address 2 will send eight 16-bit words to the supervisory PLC.
Push
<Enter>
.
Result:
The Peer Cop screen should like this:
Vedere la pagina 233