Using Peer Cop with Concept
298
870 USE 101 00 V.2.2
Changing the Peer Cop Summary Information
Overview
For our example, we will change the default Health Timeout setting to 240 ms and
the default Last Value setting to
Hold on timeout
.
Procedure
Follow the steps in the table below to change the default values, using the Peer Cop
dialog box.
Continued on next page
Step Action
1 Click the
Hold on Timeout
radio button.
Result:
The Hold on Timeout option is selected and the Clear on Timeout option
is deselected.